Risk of airway fire with the use of KTP laser and high flow humidified oxygen delivery in a laryngeal surgery model.


ABSTRACT: Airway surgery presents a unique environment for operating room fire to occur. This study aims to explore the factors of combustion when using KTP laser with high flow oxygen in an ex-vivo model. The variables tested were varying tissue type, tissue condition, oxygen concentration, laser setting, and smoke evacuation in a stainless-steel model. Outcome measures were time of lasing to the first spark and/or flame. A multivariate Cox proportional hazard model was used to determine the risk of spark and flame across the different risk factors. For every 10% increase in oxygen concentration above 60% the risk of flame increased by a factor of 2.3. Continuous laser setting at 2.6 W increased the risk by a factor of 72.8. The risk of lasing adipose tissue is 7.3 times higher than that of muscle. Charred tissue increases the risk of flame by a factor of 92.8. Flame occurred without a preceding spark 93.6% of the time. Using KTP laser in the pulsed mode with low wattages, minimising lasing time, reducing the oxygen concentration and avoiding lasing adipose or charred tissue produce a relatively low estimated risk of spark or flame.

SUBMITTER: Huang L 

PROVIDER: S-EPMC8752812 | biostudies-literature |

REPOSITORIES: biostudies-literature

Similar Datasets

| S-EPMC5563272 | biostudies-literature
| S-EPMC6797255 | biostudies-literature
| S-EPMC9259177 | biostudies-literature
| S-EPMC6553847 | biostudies-literature
| S-EPMC5901019 | biostudies-literature
| S-EPMC4835333 | biostudies-other
| S-EPMC7059285 | biostudies-literature
| S-EPMC5735892 | biostudies-literature
| S-EPMC8289652 | biostudies-literature
| S-EPMC7589281 | biostudies-literature