Fault Detection and Classification in MMC-HVDC Systems Using Learning Methods.


ABSTRACT: In this paper, we explore learning methods to improve the performance of the open-circuit fault diagnosis of modular multilevel converters (MMCs). Two deep learning methods, namely, convolutional neural networks (CNN) and auto encoder based deep neural networks (AE-based DNN), as well as stand-alone SoftMax classifier are explored for the detection and classification of faults of MMC-based high voltage direct current converter (MMC-HVDC). Only AC-side three-phase current and the upper and lower bridges' currents of the MMCs are used directly in our proposed approaches without any explicit feature extraction or feature subset selection. The two-terminal MMC-HVDC system is implemented in Power Systems Computer-Aided Design/Electromagnetic Transients including DC (PSCAD/EMTDC) to verify and compare our methods. The simulation results indicate CNN, AE-based DNN, and SoftMax classifier can detect and classify faults with high detection accuracy and classification accuracy. Compared with CNN and AE-based DNN, the SoftMax classifier performed better in detection and classification accuracy as well as testing speed. The detection accuracy of AE-based DNN is a little better than CNN, while CNN needs less training time than the AE-based DNN and SoftMax classifier.

SUBMITTER: Wang Q 

PROVIDER: S-EPMC7472012 | biostudies-literature | 2020 Aug

REPOSITORIES: biostudies-literature

altmetric image

Publications

Fault Detection and Classification in MMC-HVDC Systems Using Learning Methods.

Wang Qinghua Q   Yu Yuexiao Y   Ahmed Hosameldin O A HOA   Darwish Mohamed M   Nandi Asoke K AK  

Sensors (Basel, Switzerland) 20200808 16


In this paper, we explore learning methods to improve the performance of the open-circuit fault diagnosis of modular multilevel converters (MMCs). Two deep learning methods, namely, convolutional neural networks (CNN) and auto encoder based deep neural networks (AE-based DNN), as well as stand-alone SoftMax classifier are explored for the detection and classification of faults of MMC-based high voltage direct current converter (MMC-HVDC). Only AC-side three-phase current and the upper and lower  ...[more]

Similar Datasets

| S-EPMC11297239 | biostudies-literature
| S-EPMC9733882 | biostudies-literature
| S-EPMC9506613 | biostudies-literature
| S-EPMC7098650 | biostudies-literature
| S-EPMC10747833 | biostudies-literature
| S-EPMC6912926 | biostudies-literature
| S-EPMC4743480 | biostudies-literature
| S-EPMC10861062 | biostudies-literature
| S-EPMC8762208 | biostudies-literature
| S-EPMC10459304 | biostudies-literature